7.3.
Site of installation of the PULSAR DRY
A solid anchoring of the pump to its support base helps absorb any vibrations created by
pump operation.
Block the pipes with their own supports and connect them so that they do not exert strain,
stress or vibration on the pump inlets.
It is always good practice to position the pump as close as possible to the liquid to be
pumped.
It is recommended to fit a foot valve on intake. To avoid the formation of air pockets in the
suction pipe, ensure that the suction pipe is tilted slightly towards the electropump.
Provide a hole for priming the pump in the delivery pipe (see paragraph. 9.1).
7.4.
Working conditions of the PULSAR DRY
Water temperature: from 0°C to + 40°C.
The electropump cannot operate when dry.
Install in vertical position.
If installed in a pit, the pit must be free from frost.
PULSAR DRY
installation
below
head
Pumpland.ru
ENGLISH
filter
non return
valve
installation
on intake
Fig. 2
23
vent
pipe
supports
non return
valve
filling
cap
drainage
cap
pipe
supports
system
drainage
foot
valve
filter