Installation Instructions for Luminaire With Multi-hinge Design (Continued)
(Type I and Type III Light Distribution)
4. Use the label to determine the direction of the light and select the hinge that will orient the luminaire appropriate for
your application. NOTE: Hinge interference exists with the 90° stanchion, 25° stanchion, and wall mount hoods. Therefore,
these designs are limited to one hinge. See diagram below.
5. Hang the luminaire on the appropriate hinge; secure with the hinge pin.
6. Strip the individual conductors to bare wire and insert them into the proper terminal block connections. The connection points
are identified on the terminal block as: "L" = Line, "N" = Neutral, and "G" = Ground. Tighten down the terminal block screws
onto the wire.
7. Connect HART Configuration utility to terminals marked as 'H' meaning HART port, the connection is polarity insensitive.
8. Terminals marked as 'A' are for future use.
9. Luminaire requires bonding to mounting hood. Connect internal housing bond wire to GREEN ground screw in the mounting hood.
10. Orient the position of the SENSOR POD towards the center of the walkway.
11. Fold all excess supply leads and fasten them into the mounting hood with the wire tie (supplied) to avoid pinching the wires.
12. Swing the luminaire up and tightly secure with the hex nut and washer combination.
Installation Instructions for Through feed Wiring
For continuous row mounting, maximum allowed number of luminaires are below:
Appleton • 1.800.621.1506 • www.appletonelec.com
fIGURE 21: MULTI-hINGE WALL hOOD DETAIL
Model
IMGCL5
IMGCL9
IMGCh6
Maximum no. of luminaires
Ambient
40 C
55 C
65 C
40 C
55 C
65 C
40 C
55 C
65 C
DOC000083A000 Rev. 03 MY8278 10-MAY-22– Page 15 of 65
in series
bU Driver
31
23
11
21
15
7
11
8
4