25° Stanchion (kPS-125, kPS-150)
Dimensions:
Wall (KPWB-75, KPWB-100)
Mounting:
1. Bolt the wall hood to a structural member.
2. Remove unused conduit plugs and reinstall with tlc-3 grease applied in approximately three equal lines, spaced equally apart on
the conduit plugs.
CONDUIT ENTRY (5x)
25° Stanchion (KPS-125, KPS-150)
Installation:
1. Apply a corrosion-inhibiting grease, such as petroleum or soap-thickened mineral oils, in 3 lines, spaced approximately
Mounting:
120 degrees apart, perpendicular to the threads on the conduit.
1. Apply tlc-3 grease in approximately three equal lines, spaced equally apart on the conduit stem. thread the stanchion hood onto
2. Thread the stanchion hood onto the 1-1/4 inch or 1-1/2 inch conduit. NOTE: Five full threads must be engaged.
the 1-1/4 inch or 1-1/2 inch conduit stem. NOTE: five full threads must be engaged.
3. Determine the appropriate orientation and tighten the set screw.
2. determine the orientation and tighten the set screw.
SET SCREW
90° Stanchion (KPST-125, KPST-150)
Appleton • 1.800.621.1506 • www.appletonelec.com
Mounting:
LUMINAIRE WITh SMALL hEAT SINk
LUMINAIRE WITh LARGE hEAT SINk
fIGURE 15: LUMINAIRE WITh 25° STANChION hOOD
fIGURE 16: 25° STANChION hOOD DETAILS
DOC000083A000 Rev. 03 MY8278 10-MAY-22– Page 12 of 65