Télécharger Imprimer la page

Lenze SMD Serie Instructions De Mise En Service page 13

Masquer les pouces Voir aussi pour SMD Serie:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

3.2.4
Control terminals
Data for control connections (printed in bold = Lenze setting)
Terminal
Reference potential
7
Analog input
8
0 ... 10 V (changeable under C34)
Internal DC supply for setpoint potentiometer
9
Internal DC supply for digital inputs
20
Digital input Start/Stop
28
Digital input configurable with CE1
E1
Activate fixed setpoint 1 (JOG1)
Digital input configurable with CE2
E2
Direction of rotation
Digital input configurable with CE3
E3
Activate DC injection brake (DCB)
Relay output (normally-open contact)
K12
configurable with C08
Fault (TRIP)
K14
NOTE
LOW = 0 to +3V, HIGH = +12 to +30V.
Protection against contact
All terminals have basic isolation (single insulating distance)
Protection against contact can only be ensured by additional measures (i.e. double insulation)
STOP!
In the case of a Spinning Motor:
To bring free-wheeling loads such as fans to a rest before starting the drive, use the DC
injection braking function ("Auto-DCB"). Starting a drive into a freewheeling motor creates
a direct short-circuit and may result in damage to the drive.
Confirm motor suitability for use with DC injection braking.
Lenze 13435747 EDBSX03 v17 EN, DE, FR, IT, ES
All manuals and user guides at all-guides.com
Installation
input resistance: >50 kΩ
(with current signal: 250 Ω)
+10 V, max. 10 mA
+12 V, max. 20 mA
LOW =
Stop
HIGH =
Run Enable
HIGH =
JOG1 active
LOW =
CW rotation
HIGH =
CCW rotation
HIGH =
DCB active
AC 250 V / 3 A
DC 24 V / 2 A ... 240 V / 0.22 A
11

Publicité

loading