3.2
Electrical installation
3.2.1
Installation according to EMC requirements
EMC
Compliance with EN 61800-3/A11
Noise emission
Compliance with limit value class A according to EN 55011 if installed in a control
cabinet with the appropriate footprint filter and the motor cable length does not
exceed 10m
A Screen clamps
B Control cable
C Low-capacitance motor cable
(core/core < 75 pF/m, core/screen < 150 pF/m)
D Electrically conductive mounting plate
E Filter (if required)
3.2.2
Fuses/cable cross-sections
Type
ESMD251X2SFA ... ESMD551X2SFA
ESMD371X2TXA ... ESMD112X2TXA
ESMD152X2TXA
ESMD751X2SFA, ESMD222X2TXA
ESMD152X2SFA, ESMD302X2TXA
ESMD222X2SFA, ESMD402X2TXA
(1) Observe the applicable local regulations.
(2) Pulse-current or universal-current sensitive earth leakage circuit breaker.
(3) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, required. Bussman KTK-R, JJN, JJS or equivalent.
(4) Connection without end ferrules or with attached pin end connectors.
(5) Installations with high fault current due to large supply mains may require a type D circuit breaker.
(6) Thermomagnetic type breakers preferred.
Observe the following when using E.l.c.b:
•
Installation of E.l.c.b only between supplying mains and controller.
•
The E.l.c.b can be activated by:
- capacitive leakage currents between the cable screens during operation (especially with long,
screened motor cables)
- connecting several controllers to the mains at the same time
- RFI filters
Lenze 13435747 EDBSX03 v17 EN, DE, FR, IT, ES
All manuals and user guides at all-guides.com
Fuse
Miniature
circuit
breaker
M10 A
C10 A
M16 A
C16 A
M16 A
C16 A
M20 A
C20 A
M25 A
C25 A
Installation
(1)
Recommendations
Fuse
or
Input Power Wiring
(3)
Breaker
(L1, L2/N, L3, PE)
(6)
(5)
[mm²]
(N. America)
10 A
2.5
12 A
2.5
15 A
2.5
20 A
4
(4)
25 A
6
(4)
B
E
C
D
A
Tmd005
E.l.c.b.
(2)
[AWG]
14
14
> 30 mA
14
12
10
9