TLS2 Setup
Alarm Message Quick Reference Index
Alarm
Annual Test Fail
Autodial Fail
Delivery Needed
Gross Test Fail
High Water
Invalid Fuel Height
Low Product
Low Temperature
Max Product
Overfill
Periodic Test Fail
Probe Out
4
Table 1: Alarm Message Table
Type
Tank
In-tank annual leak test failed
Comm
System failed to connect to a remote
receiver after programmed number
of tries.
Tank
Product level dropped below preset
limit.
Tank
In-tank leak test failed.
Tank
Water detected in tank exceeds pre-
set limit.
Tank
Fuel level dropped to a point below
the minimum detectable level or only
one float is present.
Tank
Tank level dropped below preset
limit.
Tank
Probe temperature dropped below -
4°F (-20°C). For Low Temperature
probes, below -40°F (-40°C).
Tank
Product level rose above preset limit.
Tank
Potential overflow of tank may occur.
Tank
In-tank leak test failed.
Tank
Hardware failure - probe or intercon-
necting wiring to console.
Cause
Rerun in-tank leak test. If second test
fails, call for service.
Check remote receiver.
Call for delivery.
Rerun in-tank leak test. If second test
fails, call for service.
Remove water from the tank.
Call for delivery.
Call for delivery.
Probe returns to normal operation after
probe temperature rises above 0°F
(-17.7°C). For Low Temperature probes,
above -36°F (-38°C)
Stop delivery.
Stop delivery. Check for spillage.
Rerun in-tank leak test. If second test
fails, call for service.
Call for service.
Alarm Message Quick Reference Index
Action