TLS2 Setup
[101-104] Tank Limits Setup Screen 1
Legend for numbered boxes
This screen begins Tank Alarm Limits setup.
1
Max Product [101] - Alarms when the level of fluid in
the tank exceeds the volume you enter here. Allowable
range is 0-26000 gallons (0-98420 L). Default is 0. If
the value entered is 0 or full volume, this alarm is
disabled. An active Probe Low Temperature Warning
will disable this alarm. Touch the Down Arrow button to
the right of the window and enter the max product for
the tank.
2
Overfill [102] - Overfill Limit warns of a potential overfill
during a delivery. When the volume reaches this limit,
the system can activate an overfill alarm. The overfill
alarm threshold is referenced to the Max Product value.
If the Max Product value is 0, the Overfill Alarm
threshold is referenced to the Full Volume capacity.
Allowable range is 0 to 100%. Default is 0 (disabled).
An active Probe Low Temperature Warning will disable
this alarm.
3
Delivery Needed [103] - Delivery Needed warns when
the level of fluid in the tank drops to a level at which the
operator calls for a delivery. This value is a percentage
of Full Volume with an allowable range of 0 to 100%.
Default is 0% (which disables the alarm).Touch the
Down Arrow button to the right of the window and enter
a volume higher than that of the Low Product alarm.
4
Low Product [104] - Low Product warns when volume in
the tank pumps down to the level you enter here.
01-01-2000
ALL FUNCTIONS NORMAL
12:00 AM
1
[101]
2
[102]
3
[103]
4
[104]
1
2
3
4
5
Allowable range is 0-26000 gallons (0-98420 L).
Default is 0 (which disables the alarm). An active
Probe Low Temperature Warning will disable this
alarm. Touch the Down Arrow button to the right of the
window and enter this value at a volume lower than
that of the Delivery Needed alarm.
NOTE: Typically this alarm is set to the lowest level
before the pump runs dry. All dispensing should stop
when this alarm is active.
The Tank Alarm Limit Setup continues on next page.