TLS2 Setup
deactivate. The High Water value is entered as a height with the default value equal to 0. If the value is equal to 0,
the alarm is disabled. An active Probe Low Temperature Warning will disable the alarm.
Probe Out Alarm
If the console is not reliably communicating with the probe, the Probe Out alarm will activate.
Invalid Fuel Height
If the water float and the product float are too close together to provide reliable height data, the Invalid Fuel Height
alarm will activate.
Probe Low Temperature Warning
Standard Probe: If the Probe is reporting a temperature lower than -4°F (-20°C), the Low Temperature warning
will activate. If the alarm is active and the temperature rises above 0°F (-17.7°C) the alarm will deactivate.
Low Temperature Probe: Alarm -40°F (-40°C), Clear -36°F (-37.7°). When the low temperature warning is
active the High Water, Low Product, Max Product, Delivery Needed, and Overfill alarms are disabled.
Delivery Needed Alarm
When the tank's product level drops below the preset limit, the Delivery Needed alarm will activate.
Leak Test Alarm
When a Gross, Periodic, or Annual leak test fails a Gross, Periodic, or Annual Leak Test Alarm will activate. To
clear a failed leak test alarm, a passing leak test must be run.