TLS2 Setup
[105-108] Tank Limits Setup Screen 2
Legend for numbered boxes
This screen continues Tank Alarm Limits setup.
1
High Water [105] - Alarms when the level of water in the
tank exceeds the height you enter here. Set this value
at a level lower than the pickup for the submersible
pump or suction line. Allowable range is 0-9 inches (0-
228.6 mm). Default is 0 (which disables the alarm).
Touch the Down Arrow button to the right of the window
and enter the desired high water limit.
2
Delivery Delay [106] - Use this display to set a delay
time between the completion of a bulk delivery and the
Delivery Increase Report. This feature prevents
generation of multiple reports during the intervals
between multi-compartment drops to one tank. The
feature also allows fuel to "settle out" after a delivery,
which is especially important in manifolded tank groups.
Allowable delay is 1 to 60 minutes. Default is 1. Touch
the Down Arrow button to the right of the window and
enter a desired delay.
3
Ann Leak Test Min [107] - This value sets the minimum
tank volume required to record a passed annual leak
test. The value reflects federal, state, and local
requirements. This value is a percentage of Full Volume
with an allowable range of 1.0 to 100%. Default is 0
(which disables the alarm). Touch the Down Arrow
button to the right of the window and enter a volume.
42
01-01-2000
ALL FUNCTIONS NORMAL
12:00 AM
1
[105]
2
[106]
3
[107]
4
[108]
1
2
3
4
5
4
Per Leak Test Min [108] - This value sets the minimum
tank volume required to record a passed periodic leak
test. The value reflects federal, state, and local
requirements. This value is a percentage of Full
Volume with an allowable range of 1.0 to 100%.
Default is 0 (which disables the alarm). Touch the
Down Arrow button to the right of the window and
enter a volume.
The Tank Alarm Limit Setup continues on next page.
[105-108] Tank Limits Setup Screen 2