Roger Technology B70/2DC Instructions Et Consignes Pour L'installateur page 51

Masquer les pouces Voir aussi pour B70/2DC:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 90
Setting photocell mode during gate closing (FT1)
DISABLED. Photocell is not active or not installed.
STOP. The gate stops and remains stationary until the next command is received.
when the photocell is cleared.
cleared.
Photocell (FT1) mode with gate closed
If the photocell is obstructed, the gate cannot open.
The gate opens when an open command is received, even if the photocell is obstructed.
The photocell sends the gate open command when obstructed.
Setting photocell mode during gate opening (FT2)
DISABLED. Photocell is not active or not installed.
STOP. The gate stops and remains stationary until the next command is received.
when the photocell is cleared.
is cleared.
Setting photocell mode during gate closing (FT2)
DISABLED. Photocell is not active or not installed.
STOP. The gate stops and remains stationary until the next command is received.
when the photocell is cleared.
cleared.
Photocell (FT2) mode with gate closed
If the photocell is obstructed, the gate cannot open.
The gate opens when an open command is received, even if the photocell is obstructed.
The photocell sends the gate open command when obstructed.
Enable close command 6 s after activation of photocell (FT1-FT2)
N.B.: This parameter is not visible if
or
is set.
Disabled.
Enabled. When the photocell gate FT1 is crossed, a close command is sent 6 seconds later.
Enabled. When the photocell gate FT2 is crossed, a close command is sent 6 seconds later.
Setting motor stop distance
Select number of motors installed
1 motor.
51

Publicité

Table des Matières
loading

Table des Matières