10. Technical data
CE mark
This unit complies with the legal requirements laid out
within the EU regulations
Certificate number
DMT 99 ATEX 062
Max. ambient
temperature
T5 = +60°C
Peak values in fault condition
Input voltage
15 V
Short circuit current
31 mA
Capacitance
C
i
Inductance
L
i ≤
38
≅ 0 µF
2 µH