Fault Finding; Fault Messages; Fault Analysis - Endress+Hauser PROFIBUS-PA RID 261 Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7. Fault finding

7. Fault finding

7.1 Fault messages

Message
Meaning
Process value transmission
faulty, process value is
incomplete.
10 s no valid process value,
no slave with this address
Unit defective
Process value too high, or
incorrect offset set up.
flashing
Process value status
contains a non defined
value, no valid process
value or status BAD

7.2 Fault analysis

Fault
No indication in the display
Process value of the bus user and
the display are not identical
Cure
Check the offset settings in the
PROFIBUS-PA display and the
configuration of the bus user selected.
(6.2)
Match the PROFIBUS-PA display
address with the address of the bus
user selected (6.2).
Check the offset settings in the
PROFIBUS-PA display.
Unit exchange is required
Check the configuration of the bus user
selected and the offset settings in the
PROFIBUS-PA display (6.2).
Check the offset settings in the
PROFIBUS-PA display. Make sure that
the process value status contains
defined values on data transmission
from master to bus user (6.2).
Fault cure
Check power supply from the bus
Unit defective (CPU or terminal board),
please send back to manufacturer
Check the offset settings in the
PROFIBUS-PA display.
Match the address of the PROFIBUS- PA
display with the address of the selected
bus user.