Jaga DBH SET Manuel page 95

Masquer les pouces Voir aussi pour DBH SET:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Enkel bij configuratiecode DPC.HC6220!
The unit starts as soon as the water temperature is <
24°C and the control signal is 0-10V.
Activator speed in function of the incoming control
signal.
B2.1.2.  With control pannel
Off
The user manually selects the desired mode via the control panel . The unit can run at
3 speeds. The unit starts as soon as there is a 0-10V control signal and the set water temperature has
been reached.
The unit start at the last selected speed (1, 2 of 3) if there
is a 0-10V control signal. en de water temperature > 28 ̊ C .
Only with configuration code DPC.HC6523!
The unit start at the last selected speed (1, 2 of 3) if there is a
0-10V control signal. en de water temperature < 24 ̊ C .
Off
All functions are disabled until the user switches on the
unit via the control panel.
Activator speed is set according to the unit's
length.
Control
MODE
Tw < 24ºC
MODE
Speed 1
Blue LEDs
are flashing in the set mode: the water temperature of the supplied water is too high (Tw > 24
̊ C ).
Red LEDs
are flashing in the set mode: the water temperature of the supplied water is too low (Tw < 28 ̊ C ).
B2.2.  OPTION : THERMO-ELECTRICAL MOTOR
–  Valve opens in heating and cooling mode as soon as there is a control signal > 1V.
–  Valve closed in off mode & when the control signal is 0V.
- DPC.HC6423 / DPC.HC6523
MODE
Tw > 28ºC
MODE
Speed 2
Max
Min
0
1
curve : Speed versus 0-10V control signal
S3
S2
S1
Min
0
1
curve : Speed versus 0-10V control signal
MODE
Off
MODE
Speed 3
BMS (V)
10
EN
BMS (V)
10
95

Publicité

Table des Matières
loading

Table des Matières