gb | 7. Mounting (specialist installer)
Ensure minimum spacing of 300 mm
between the ceiling and centre of the wall
opening and minimum spacing of 200 mm
between the side and centre of the wall
opening.
The wall opening (core drill hole) must be
at least 220 mm in diameter.
The minimum wall thickness must be 270
mm.
i
Tools and material to be provided
by the customer:
Core hole drill and drill bit
220 mm in diameter
Metal saw
Hand saw
Cutter blade
Construction foam, not pressing
Silicone for outdoor use
Internal cover mounting:
4 x dowels and screws, 6 mm in
diameter
External wall mounting:
4 x dowels and screws, 6 mm in
diameter (length and dowel type
depending on external wall version /
insulation system)
Soffit element mounting:
6 x polystyrene dowels / insulation
material dowels and screws, 5 mm in
diameter (length and dowel type
depending on insulation thickness)
Cable clip
NYM-O or NYM-J connecting ducts 1.5
mm², 3 wires
J-YSTY control cables
0.8 mm, 4 wires
 
32

7. Mounting (specialist installer)

7.1 Information
DANGER
Danger from electric shock!
Deactivate the fuse in the fuse box and
protect against being accidentally switched
back on. Fit a warning notice on the fuse
box.
Installation work may only be carried out
by authorised specialists.
Make sure there is sufficient working
space in front of the unit, e.g. for filter
changing.
In order to avoid any smells, there
should be sufficient space between the
outside air inlet for the ventilation unit
and the sewerage vent on the roof.
Select the installation position so that
contamination and draughts are
avoided.
Recommendation for the prevention of
dirt deposits on the façade near the
external cowl: Fit a water-repellent
plastering system to the façade.
Produce a core drill hole with a
1...2 % inclination from the inside out.
Condensation can then drain outwards
and drip off via the drip edge of the
external cover.
Do not fit the units and room air control
near showers (no splash protection).

7.2 Wall insulation sleeve

Observe prescribed minimum
i
spacing between ventilation unit
and ceiling (≥ 300 mm) and side
(≥ 200 mm). Also refer to
Chapter 6.3, page 31.