intervene when the value at which it has been set is reached, and
E
bring the burner to a standstill. When the temperature (pressure, if
steam boiler) drops below the intervention limit of the "shut down"
N
device, the burner will start up again as previously described.
During normal operations, the thermostat (or pressure switch) of the
G
2nd stage is aware of load variations in the boiler and automatically
L
requests the servomotor regulating delivery (fuel/air) to make an
adjustment in the fuel delivery and in the relative combustion air.
I
With this manoeuvre, the delivery regulating system (fuel/air)
reaches a position of equilibrium which corresponds to a fuel de-
S
H
BASIC HYDRAULIC DIAGRAM FOR MODULATING BURNERS FUNCTIONING WITH
DENSE FUEL OIL
C o n n e c t i o n t o t h e
f e e d i n g
c i r c u i t f o r
o n e o r m o r e b u r n e r s .
see 0002901120, 8511/6,
8513/7
1
FILTER
2
BURNER PUMP (20-22 BAR)
3
PRESSURE GAUGE O-40 BAR
4
ATOMIZER BODY
5
RETURN NOZZLE WITHOUT PIN
6
RODS WITH CLOSING PINS
7
BY PASS HOLES
8
CLOSING SPRINGS
9
OPENING ELECTROMAGNETICS
10 RETURN PRESSURE REGULATOR MIN=10-12 BAR MAX=18 - 20 BAR
11 MODULATION SERVOMOTOR
12 AIR/FUEL REGULATION CONTROL DISK
All manuals and user guides at all-guides.com
livery and a relative combustion air delivery equal to the quantity
of heat required by the boiler. It should be kept in mind that the
field of variation in output obtainable with a good combustion is,
as an indication, from 1 to 1/3 of the maximum output given on
the rating plate.
Note: The air pressure switch must be set when the burner
13 AIR LOCKS
14 FLEXIBLE TUBE
15 ELECTRIC PREHEATER
16 SELF-CLEANING FILTER 0.3 MM
17 THERMOMETER
18 PREHEATER MINIMUM THERMOSTAT
19 PREHEATER MAXIMUM THERMOSTAT
20 PREHEATER REGULATION THERMOSTAT
21 NOZZLE RETURN THERMOSTAT
22 PUMP HEATING RESISTANCE
23 HEATING RESISTANCE 60W
24 HEATING RESISTANCE 20W
12 / 30
0006080118_200811
is started up and must be in function with the pressure
value verified during operation with the ignition flame.