FUEL SUPPLY SYSTEM

E
The burner pump must receive fuel from a suitable supply circuit,
including an auxiliary pump with pressure adjustable from 0,5 to
N
2 bar. Fuel must be pre-heated to 50÷ 60° C.
G
The supply pressure value of the fuel at the burner pump (0,5 ÷
5 bar) must not vary either when the burner is not in operation or
L
when it is operating at the maximum level fuel supply called for
by the boiler.
I
The supply circuit must be built according to our drawings n° BT
S
H
All manuals and user guides at all-guides.com
8511/6 or BT 8513/7 even when low viscosity fuel is being used.
Pipe dimensions depend on their length and the capacity of the
pump being used.
Our instructions only regard what is necessary for ensuring good
operation.
The regulations to be observed in order to comply with antismog
laws as well as the local Firemen's' regulations, should be refer-
red to in the relevant publications.
Fuel Viscosity / Temperature Graph
10 / 30
0006080118_200811