Télécharger Imprimer la page

nVent RAYCHEM C-150-E Mode D'emploi page 3

Publicité

nVent RAYCHEM C-150-E
Hazardous Locations
(1)
DEKRA 20ATEX0011U
IECEx DEK 20.0005U
ТС RU C-BE.МЮ62.В.00054/18
Ex e IIC Gb U Ex tb IIIC Db U
Ta –55°C...+150°C Power ON IP66
Ta –55°C .. +200°C Power OFF
ООО "ТехИмпорт"
Ex eb IIC Gb
BAS21UKEX0658U
Ex tb IIIC Db
Ex eb IIC T* Gb;
Class I Zone 1 AEx eb IIC T* Gb
Ex tb IIIC T* °C Db;
Zone 21 AEx tb IIIC T*°C Db
* For system Temperature Code, see heating cable or design
documentation./ Temperaturklasse des Systems siehe Heizband-
oder Auslegungsdokumentation./Pour le code de température du
système, voir le câble chauffant ou la documentation technique./ Zie
voor de Temperatuurcode van het systeem de documentatie over de
verwarmingskabel of het ontwerp./ For systemtemperaturkode, se
varmekabel- eller konstruksjonsdokumentasjon./ För systemtemperaturkod,
se värmekabel- eller designdokumentation/ Se i dokumentationen til
varmekablet eller konstruktionen vedrørende systemets temperaturkode./
Järjestelmän lämpötilakoodi on merkitty lämmityskaapeliin tai
suunnitteluasiakirjoihin./ Per il Codice Temperatura del sistema, vedere la
documentazione di progetto o del cavo scaldante./ Para ver información
sobre el código de temperatura, consulte la documentación del cable
de calentamiento o del diseño./ Kod temperatury systemu - patrz
dokumentacja przewodu grzewczego lub dokumentacja projektowa./
Для определения температурного класса истемы см. маркировку
греющего кабеля или проектную документацию./ Kód teploty systému
viz topný kabel nebo projektovou dokumentaci./ A rendszer hőmérsékleti
kódjáért lásd a fűtőkábel- vagy a tervezési dokumentációt./ Za šifru
temperature sustava, vidi grijaći kabel ili projektnu dokumentaciju.
(1) Hazardous Locations: Ex-Bereiche/ Zones explosibles/ Gevaarlijke
locaties/ Farlige områder/ Farlig plats/ Farlige områder/ Vaaralliset tilat/
Zone pericolose/ Ubicaciones de riesgo/ Strefy zagrożone wybuchem/
Опасные места/ Nebezpečná prostředí/ Veszélyes helyszínek/
Opasne lokacije
II 2 G Ex eb IIC Gb
II 2 D Ex tb IIIC Db
ENGLISH
WARNING: To prevent electrical shock or fire, this product
must be installed correctly. Water ingress must be avoided
before and during the installation.
De-energise circuits before installation or servicing.
Maximum nominal current rating of over-current protection: 40 A.
Persons involved in the installation and testing of electric
heat tracing systems shall be suitably trained in all special
techniques required. Installation shall be carried out under the
supervision of a qualified person.
Ground fault equipment protection must be used on each
heating cable circuit as arcing may not be stopped by
conventional circuit breakers. Before installing this product,
read the instructions completely.
Keep ends of heating cables and kit components dry before
and during installation.
The electrically conductive covering (braid) of the heating
cable shall be connected to a suitable earthing terminal.
The presence of the heating cables shall be made evident
by the posting of caution signs or markings at appropriate
locations and/or at frequent intervals along the circuit.
The insulation resistance of the heating cable shall be
measured and recorded after installation and shall not be less
than 20 MOhm.
WARNING: The purchaser should make the manufacturer
aware of any external effects or aggressive substances that
the equipment may be exposed to.
CAUTION: Prolonged or repeated contact with the
sealant in the core sealer may cause skin irritation. Wash
hands thoroughly. Overheating or burning the sealant will
produce fumes that may cause polymer fume fever. Avoid
contamination of cigarettes or tobacco. Consult MSDS VEN
0058 for further information.
Schedule of limitations
The maximum surface temperature depends on the
configuration of the heat tracing system, determined in
accordance with IEC/IEEE 60079-30-1.
Rated Voltage: 277 V
Rated Current: 40 A
Minimum ambient temperature: –55°C
Maximum ambient temperature: +55°C
Maximum operating temperature, power "on": +150°C
Maximum exposure temperature, power "off": +200°C
Installation instruction for low profile power connection kit
C-150-E. For use with all nVent RAYCHEM BTV-, QTVR-, XTV-
and KTV-heating cables.
C-150-E for use with power supply cables with
following properties:
Conductor type:
Amount of conductors:
Environmental protection:
Minimum conductor size:
Maximum conductor size:
Minimum outer diameter:
Maximum outer diameter:
semi flexible / rigid
2 conductors shielded or 3
conductors unshielded
outer sheath / over jacket
1.0 mm² (17 AWG)
4.0 mm² (11 AWG)
6.8 mm
12.6 mm
nVent.com/RAYCHEM | 3

Publicité

loading