Increasing The Fan Speed - Sanyo Classic PAC i SPW-C256VH Instructions D'installation

Climatiseur réversible dc inverter
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 92
3-21-1. Installing the Air-Intake Filter
(This Page is Only for Spanish Version.)
(1) Standard installation
Install the filter onto the intake port. (Fig. 3-72)
Outlet duct
1
Intake port
(2) If a duct is connected to the intake port:
First remove the bottom cover, and then install
the filter inside the unit. (Fig. 3-73)
Intake port
1
Remove the bottom cover
2
in order to remove or install the filter.
Filter
Bottom cover
(3) If the intake is on the bottom:
Remove the intake port chamber from the side, and then
reattach the chamber onto the bottom of the unit.
(Fig. 3-74)
Remove the
bottom cover
and install it
onto the side.
2
1
Intake port
Install the side intake port chamber onto the bottom.

3-22. Increasing the Fan Speed

If external static pressure is too great (due to long extension
of ducts, for example), the air flow volume may drop too low at
each air outlet. This problem may be solved by increasing the
fan speed using the following procedure:
(1) Remove 4 screws on the electrical component box and
remove the cover plate.
(2) Disconnect the fan motor sockets in the box.
(3) Take out the booster cable (sockets at both ends) clamped
in the box.
(4) Securely connect the booster cable sockets between the
disconnected fan motor sockets in step 2 (Fig. 3-75).
Electrical component box
Booster cable
Fan
motor
Fan motor socket
(At shipment)
(5) Place the cable neatly in the box and reinstall the cover
plate.
2
Outlet duct
Outlet duct
Filter
Booster cable
(Booster cable installed)
Indoor Fan Performance
150
100
50
0
Fig. 3-72
150
100
50
Fig. 3-73
0
Air Flow (m
150
100
Fig. 3-74
50
0
20
Air Flow (m
N OTE
■ How to read the diagram
The vertical axis is the external static pressure (Pa) while
the horizontal axis represents the air flow (m
characteristic curves for "HT", "H", "M" and "L" fan speed control
are shown. The nameplate values are shown based on the
"H" air flow. For the 25 type, the air flow is 18 m
the external static pressure is 49 Pa at "H" position. If external
static pressure is too great (due to long extension of ducts,
for example), the air flow volume may drop too low at each air
Fig. 3-75
outlet. This problem may be solved by increasing the fan speed
as explained above.
31
12 Type
150
15
10
100
HT
5
50
H
M
L
0
0
5
10
3
Air Flow (m
/minute)
25 Type
15
150
10
100
HT
H
5
50
M
L
0
0
10
20
3
/minute)
48 Type
15
150
10
100
HT
H
5
50
M
L
0
0
30
40
18
3
/minute)
HT : Using the booster cable
H : At shipment
16, 18 Type
15
10
5
HT
H
M
L
0
10
15
3
Air Flow (m
/minute)
36 Type
15
HT
10
H
5
M
L
0
20
30
3
Air Flow (m
/minute)
60 Type
15
HT
10
H
5
M
L
0
22
26
30
34
38
42
3
Air Flow (m
/minute)
Fig. 3-76
3
/minute). The
3
/minute, while