Sanyo Classic PAC i SPW-C256VH Instructions D'installation page 74

Climatiseur réversible dc inverter
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 92
System address
No.
0 Automatic address
(Setting at shipment = "0")
1 (If outdoor unit is No. 1)
2 (If outdoor unit is No. 2)
11 (If outdoor unit is No. 11)
21 (If outdoor unit is No. 21)
30 (If outdoor unit is No. 30)
10-22-3. Checking indoor unit addresses
Use the remote controller to check the addresses of the indoor
units. Press and hold the
seconds or longer (simple settings mode, "ALL" appears on the
remote controller). Then press the
indoor address.
(For the system addresses of the No. 1 outdoor unit, each time the
button is pressed, the address changes as follows: 1-1, 1-2, ...)
The indoor unit fan operates only at the selected indoor unit.
Confirm the indoor unit address. (For the system addresses of
the No. 2 outdoor unit, the displayed addresses are 2-1, 2-2, ...)
Press the
button again to return to the normal remote
controller mode.
10-22-4. Indicating (marking) the indoor and outdoor unit
combination number
Indicate (mark) the number after automatic address setting is
completed.
(1) So that the combination of each indoor unit can be easily
checked when multiple units are installed, ensure that the
indoor and outdoor unit numbers correspond to the system
address number on the outdoor unit control PCB, and use
a magic marker or similar means which cannot be easily
removed to indicate the numbers in an easily visible location
on the indoor units (near the indoor unit nameplates).
Example: (Outdoor) 1 – (Indoor) 1, 2...
(Outdoor) 2 – (Indoor) 1, 2...
System address
System address
10s digit
1s place
(2P DIP switch)
(Rotary switch)
Both OFF
"0" setting
ON
ON
1
2
OFF
Both OFF
"1" setting
ON
ON
1
2
OFF
Both OFF
"2" setting
ON
ON
1
2
OFF
10s digit ON
"1" setting
ON
ON
1
2
OFF
20s digit ON
"1" setting
ON
ON
1
2
OFF
10s digit and 20s
digit ON
"0" setting
ON
ON
1
2
OFF
button and
button for 4
button and select the
(2) These numbers will be needed for maintenance. Be sure to
indicate them.
■ K Type (for Link Wiring)
10-23. Caution
This unit may be used in a single-type refrigerant
system where 1 outdoor unit is connected to 1 indoor
unit, and also in a system where 1 outdoor unit is
connected to multiple indoor units (maximum 4).
If link wiring is used, set the outdoor unit system address
to allow the combination of indoor and outdoor units to be
identified. At the same time, indicate the indoor-outdoor unit
combination number in a location where it can be checked
easily (near the indoor unit nameplates). (This number will
be required for subsequent maintenance. Refer to 10-26-3,
4.)
Request that the customer be present when the test run is
performed. At this time, explain the operation manual and
have the customer perform the actual steps.
Be sure to pass the manuals and warranty certificate to the
customer.
Check that the 220 – 240 V AC wiring is not connected to the
inter-unit control wiring connector terminal.
If 220 – 240 V AC is accidentally applied, the indoor or
outdoor unit control PCB fuse (0.5 A for both indoor and
outdoor units) will blow in order to protect the PCB. Correct
the wiring connections, then disconnect the 2P connectors
(indoor: blue, OC) (outdoor: blue, serial 1) that are
connected to the PCB, and replace them with 2P connectors
(indoor: brown, EMG) (outdoor: brown, serial 2).
If operation is still not possible after changing the brown
connectors, try cutting the varistor (black) (both indoor and
outdoor).
(Be sure to turn the power OFF before performing this work.)
Indoor unit control PCB
2 HP
3 HP
Fig. 10-20
72
Varistor (black)
VA002
Fuse (0.5A)
CHK (2P plug)
SW103
2P connector (brown)
2P connector (blue)
Fuse (0.5A)
2P connector (blue)
2P connector (brown)
SW103
Varistor (black)
VA002
CHK (2P plug)
ON
OFF
TEST
TEST
ON
OFF

Publicité

Table des Matières
loading

Table des Matières