The following instructions are intended only for technical personnel specialised in heating units manufactured by
COLA.
Changing the parameters in a non-appropriate way can cause serious damage to people, the units and
the environment. In this case, Cola s.r.l. declines any liability.
To access the INSTALLER SETTINGS menu, press button P3 - MENU and use the scroll buttons to display the item
INSTALLER SETTINGS and then press button P3 - MENU. Use the scroll buttons to display access key 10 and
press button P3 - MENU.again.
The various parameters can be displayed with the scroll buttons; access with button P3 - MENU, edit them with the
scroll buttons and exit with ESC.
It contains the adjustment parameters given below.
Parameter code
10-01
10-02
10-03
10-04
10-05
10-06
10-07
For increasing or decreasing auger OFF duration for all powers.
For increasing or decreasing fume extractor speed for all powers, by a
value of 5% for each unit.
Enable key lock.
Adjustment probe temperature setting ON/OFF delta (see parameter
10-07)
Stove shutdown delay.
Valid only in case of Standby set to ON.
For enabling self-calibration.
For selecting the probe on which stove adjustment is to be set:
- S-AMBI: Ambient probe on stove, connected to the mainboard
- C-I084: Remote graphic display
- T-AMBI: 'Normally open' external ambient thermostat
- T-PUFFER: 'Normally open' external thermostat located on the hot
water storage tank (puffer)
- S-MAND: External probe located on the outlet and connected to the
mainboard
- S-PUFFER: Probe located on the hot water storage tank (puffer) and
connected to the mainboard.