Read Immediately

1.1 Important Information

ATTENTION!
When operating or maintaining a heat pump, the legal requirements of the
country where the heat pump is operated apply. Depending on the
refrigerant quantity, the heat pump must be inspected for leaks at regular
intervals by a certified technician, and these inspections must be
recorded.
ATTENTION!
The unit is not suited for operation with a frequency converter.
ATTENTION!
During transport, the heat pump must not be tilted more than 45° (in
either direction).
ATTENTION!
The heat pump and transport pallet are only connected by the packaging
film.
ATTENTION!
The air intake and discharge openings must not be restricted nor
obstructed.
ATTENTION!
Clockwise phase sequence (in the case of multiphase units) must be
ensured: Operating the compressor in the wrong sense of rotation, may
result in damage to the compressor. An incorrect phase sequence causes
the fan to operate in the wrong sense of rotation leading to a significant
reduction in performance.
ATTENTION!
Do not use any cleaning agents containing sand, soda, acid or chloride as
these may damage the surface.
ATTENTION!
To prevent the formation of deposits (e.g. rust) in the plate heat
exchanger of the heat pump, we recommend using an appropriate
corrosion protection system
ATTENTION!
To prevent consequential damage it is imperative that the water circuit be
neutralized after cleaning using appropriate agents.
ATTENTION!
Prior to opening the unit it must be ensured that all electrical circuits are
disconnected from the power supply.
ATTENTION!
Work on the heat pump may be done only by an authorized and qualified
customer service.

1.2 Intended Use

This device is only intended for use as specified by the manufac-
turer. Any other use beyond that intended by the manufacturer is
prohibited. This requires the user to abide by the manufacturers
product information. Please refrain from tampering with or alte-
ring the device.
EN-2
All manuals and user guides at all-guides.com
1.3 Legal Provisions and
This heat pump is designed for use in a domestic environment
according to Article 1, Paragraph 2 k) of EC directive 2006/42/EC
(machinery directive) and is thus subject to the requirements of
EC directive 2006/95/EC (low-voltage directive). It is thus also in-
tended for use by non-professionals for heating shops, offices
and other similar working environments, in agricultural establish-
ments and in hotels, guest houses and similar / other residential
buildings.
This heat pump was designed and built in compliance with all rel-
evant EU directives, DIN and VDE regulations (see CE Declara-
tion of Conformity).
The electrical connection of the heat pump must be performed
according to and conforming with all relevant VDE, EN and IEC
standards. Beyond that, all technical connection requirements of
the local electrical utility company have to be adhered to.
On connecting the heating system, all relevant regulations have
to be heeded.
Persons, especially children, who are not capable of operating
the device safely due to their physical, sensory or mental abilities
or their inexperience or lack of knowledge, must not operate this
device without supervision or instruction by the person in charge.
Children must be supervised to ensure that they do not play with
the device.
When operating or maintaining a heat pump, the legal requirements of the
country where the heat pump is operated apply. Depending on the
refrigerant quantity, the heat pump must be inspected for leaks at regular
intervals by a certified technician, and these inspections must be
recorded.
1.4 Energy-Efficient Use of the
By purchasing this heat pump you contribute to the protection of
the environment. A prerequisite for energy-efficient operation is
the proper design of the heat source system and the heat utiliza-
tion system.
One of the most important factors of heat pump efficiency is
keeping the temperature difference between the heating water
and the heat source as small as possible. It is therefore strongly
recommended that the design of both the heat source system
and the heat distribution system be carried out with great care. A
1 Kelvin (1 °C) higher temperature difference corresponds
to an increase in power consumption of approx. 2.5%. When
designing the heating system care must be taken that special ap-
plications such as domestic water heating are taken into consid-
eration and dimensioned for low temperature operation. Heat
pumps are optimally suited for underfloor heating (surface/ra-
diant heating) applications due to the low supply temperatures
(30 °C to 40 °C).
During operation it is essential that the heat exchangers are not
contaminated as this would increase the temperature difference
resulting in a lower coefficient of performance.