Loosen the lock nuts (1).
3. Switch on the power supply.
The transmitter and corresponding receiver of a gas warning system must be set to the same communication channel. If
multiple gas warning systems are installed, the transmitters of which could interfere with adjacent receivers, a different
channel should be chosen for each gas warning system. Dräger recommends installing the systems in such a way that the
flash direction of one system is opposite to the flash direction of the other system.
The channels 0 - 11 are available on the receiver.
If the transmitter TX S is being used, channels 0 to 7 must be used. If the transmitter TX L is being used, channels 8 to 11
must be used.
4. Set the communication channel on the transmitter:
a. Connect the Pulsar Interface Adapter to the communication port and switch on the communication mode.
®
b. Connect the HART
c. Establish communication on the HART
d. In the main menu, select 3 / Device Info & Config.
e. In the 3 / Device Info & Config menu, select 1 Channel.
f. Enter the communication channel.
g. Transfer the configuration change to the transmitter.
®
h. Exit the HART
application.
5. Set the same communication channel on the receiver.
a. Connect the Pulsar Interface Adapter to the communication port and switch on the communication mode.
®
b. Connect the HART
c. Establish communication on the HART
d. In the main menu, select 4 / Meas. Config.
e. In the 4 / Meas. Config menu, select 1 Channel.
f. Enter the communication channel.
g. Transfer the configuration change to the receiver.
1
handheld terminal to the Pulsar Interface Adapter.
®
handheld terminal via the Device Description.
handheld terminal to the Pulsar Interface Adapter.
®
handheld terminal via the Device Description.
1
1
Operation
en
05300114_33451
53