Power supply of the gas warning system via the TX transmitter (see Fig. A on Page 49)
Power supply of the gas warning system via the RX receiver (see Fig. B on Page 49)
Power supply for TX transmitter and RX receiver (see Fig. C on Page 49)
TX
A
C
1
Control unit and power supply
A
Instrument cable of the transmitter
B, E
Line between transmitter and receiver
C, F, G
Line to the control unit
D
Instrument cable of the receiver
4. Calculate the necessary cross-sections in accordance with the chosen cable lengths and the power intake of the transmitter
and receiver. An operating voltage of 18 V - 32 V must be present on the terminals of the transmitter and receiver.
In determining the cable lengths and the cable cross-section, the power supply must not be less than 18 V on the terminal
box (Power (+) to Power (-)).
The impedance of the 4 to 20 mA signal loop must not exceed 500 ohms.
®
If HART
is used, the 4 to 20 mA signal loop must not fall below an impedance of 230 ohms. Observe the safety manual
(9033709).