Intended use
The Wilo-Para MAXO-G and the Wilo-Para MAXO-R can be used in heating or air-
conditioning systems designed in accordance with IEC 60335-2-40. The permitted
refrigerants are limited to those listed as compatible according to
IEC 60335-2-40:2018-01.
Coolant
Safety class
Name
R-32
A2L
R-50
A3
R-142b
A2L
R-143a
A2L
R-152a
A2
R-170
A3
R-E170
A3
R-290
A3
R-444B
A2L
R-444A
A2L
R-447B
A2L
R-451A
A2L
R-451B
A2L
R-452B
A2L
R-454A
A2L
R-454B
A2L
R-454C
A2L
R-457A
A2L
R-600
A3
R-600a
A3
R-1270
A3
R-1234yf
A2L
R-1234ze(E)
A2L
62
Max. permissible surface
temperature according to
IEC 60335-2-40:2018-01
(°C)
700
545
650
650
355
415
135
370
700
700
700
700
700
700
700
700
700
700
265
360
355
700
700
Para MAXO-G
Para MAXO-R
Pictogram on the
Pictogram on the
pump:
pump:
Compatible
Compatible
not permitted
Compatible
not permitted
Compatible
not permitted
Compatible
not permitted
not permitted
not permitted
Compatible
not permitted
not permitted
not permitted
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
Compatible
not permitted
not permitted
not permitted
not permitted
not permitted
not permitted
Compatible
Compatible
Compatible
Compatible