Combustion is clean and stable when combustion values are as
follows:
Bacharach index: 0 (white)
CO
: 11 ÷ 12,5 %
2
Oxygen (O
): 4,5 ÷ 6 %
2
CO
: 500 ppm
max
You may have to change the burner settings due to the fuel used
and/or installation conditions (high altitude, air suction pipe with or
without Snorkel, etc.) if combustion parameters are not correct.
When inspection tests are completed, the hole drilled for the probe
must be sealed with a material that is resistant to high temperatures
and that ensures the tube remains airtight.
5. OPERATING INSTRUCTIONS
5.1. START
To start the heater:
• Make sure the switch (a) is set to "0";
• Supply electrical power to the space heater by pulling up the
disconnecting switch on the electric power panel: the green lamp
(b) will light up indicating that power is being supplied to the panel;
•Turn switch (a) to position H or H+V: the burner will begin the start-
up and pre-wash cycle, after which the flame will ignite; after the
combustion chamber has been heating for a few minutes, the main
fan will start up;
Warning
The fan runs continuously in H+V mode, even when the
desired room temperature has been reached, and the
burner turns off.
Warning
In H mode, the fan only runs when the combustion chamber
is sufficiently hot. Therefore, when the desired room
temperature has been reached, the burner turns off and the
fan keeps running only until the combustion chamber has
cooled completely.
• If the heater does not work during the start cycle or work cycle,
consult "TROUBLESHOOTING" to find the cause of the malfunction.
Warning
If the burner goes into safety stop (lamp c) push reset
button (g) for 3 seconds to restart the heater.
Warning
If the safety thermostat goes into safety stop (lamp d),
push reset button (f) for 3 seconds to restart the heater.
Warning
NEVER do more than two restarts in a row: unburned fuel
can accumulate in the combustion chamber and suddenly
flare up at the next restart.
5.2. STOP
Stop the heater by turning switch (a) to "0" position or, if the heater is
in automatic mode, by setting the room thermostat to a lower
temperature: the burner shuts off. The fan keeps working, starting
and stopping several times until the combustion chamber has cooled
completely.
Warning
Never stop the heater by simply turning off the
disconnecting switch on the panel.
The electrical supply must be disconnected ONLY when the
fan has come to a complete stop.
5.3. VENTILATION
To run the heater only in continuous ventilation mode, turn switch (a)
to the position with the symbol V.
L-L 277.00-SO
EN
5.4. TEMPERATURE CONTROLLER
The heater is equipped with a room thermostat (e) with LCD screen,
which displays and controls the room temperature.
The screen displays the measured temperature in [°C]:
To set the desired temperature level:
• Press the button
"SP" and the set temperature alternatively appear .
• Modify the set temperature pressing buttons
• Press button
to confirm the set temperature.
Warning
All of the operations described in this section must be
performed by professionally qualified personnel only.
The following procedures must be done at regular intervals to ensure
efficient operation of the heater. Make sure you have detached the
electrical power line from the heater before starting any work.
Warning
Before doing any maintenance:
• Stop the heater as indicated in the "STOP" paragraph;
• Switch off the power supply by means of the cut-off on
the electrical panel;
• Wait until the heater cools.
Procedure
Check heater
Check diesel supply line
Clean exterior of heater
Clean motor and fan
Check electrical connections
Check and test burner
Check thermostats
Clean interior of heater
Inspect and clean chamber
6.1. CHECKING THE HEATER AND THE DIESEL SUPPLY LINE
Perform the following checks:
• Make sure the heater is not installed where there may be a risk of
fire or explosion
• Make sure that flammable materials are kept a safe distance away
and then release it: on the screen the initial
and
6. MAINTENANCE
Periodic maintenance
X
X
X
X
.
X
X
X
X
X
24 / 44