Palazzetti Ecomonoblocco MX 25:9F Notice D'installation Et D'entretien page 60

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

2
5) Slide out and extract the panels (1) (Fig. 33).
1
6) After cleaning, reassemble referring to sec-
tion "Deflector assembly" on page 53.
60
10.3.7 maintenance of the smoke system
If there are horizontal sections, it is necessary to
check and remove any deposits of ash and soot
before they obstruct the passage of fumes.
The incrustations inside the flue affect the
optimum forced draught. When they reach a
thickness of 5-6 mm, with high temperatures
and sparks, they can ignite with easily imagina-
ble consequences both for the flue and for the
house.
10.3.8 Appliance maintenance
To be carried out at least once a year, or every
time the appliance signals maintenance request.
During the maintenance operation, the techni-
cian must:
Fig. 32
• clean the flue gas transit area thoroughly and
completely;
• check the condition and tightness of all the
seals;
• check the condition of all internal components
and make sure they are clean;
• make sure the flue gas outlet connection is
sealed and clean;
• check the correct operation of the appliance.
Fig. 33
004778930 - 06/12/2021

Publicité

Table des Matières
loading

Table des Matières