• Report any defects/damage to the supplier immediately.
1.5 Place of installation
In rooms without weather exposure.
Avoid direct sunlight exposure.
Avoid dust.
GB
Keep away from strong electromagnetic fields.
Keep away from combustible material.
Provide sufficient cooling. Install fans when installing the frequency
inverter inside an enclosed cabinet.
Altitude of installation: ≤ 4000 m, above 1000 m with reduced power
(reduced output current).
Ingress protection rating of frequency inverter: IP20. Use of the device in
explosive atmospheres is not permitted.
The frequency inverter produces noise. For this reason it should be
installed in areas where usually people do not stay for a long time.
Noise emission in operation is < 85 dB(A) in the case of sizes 1 through 7.
1.6 Operating conditions
• Size 1...7:
o Ambient temperature: 0...55°C, as from 40°C, power reduction of
2.5% / K should be considered.
• Rel. humidity: 15 ... 85 %; not condensing
• Ambient pressure: 70 ... 106 kPa
• The frequency inverter may be operated in TN, TT and IT grid types.
Operation in a corner-grounded TN grid shall not be permissible.
• Environment specification: Pollution degree 2 and overvoltage category III
(IEC 60664-1 /DIN VDE 0110-1) up to 2000 m installation altitude. Above
2000 m installation altitude overvoltage category II.
• The frequency inverter may connect to power supply every 60 s. If the unit
switches on more frequently, it may be damaged. You must consider this
when operating a mains contactor in jog operation mode.
• Short Circuit Current Rating (SCCR) according to UL 61800-5-1:
54
up to 160 kW device power (Size 7): 5 kA;
Quick Start Guide ACT
12/20