SETTING THE OPERATION PARAMETERS
Y
ATTENTION! After re-setting the end positions and, if additional settings were previously per-
formed to deactivate input SE and / or input PH (section 7.1 and / or section 7.2), it is necessary
to test the safety device operation connected to the inputs mentioned. Testings are described in
table 5 (DIP9, DIP10 switch). If necessary, repeat the additional setting to deactivate the input.
7.
SETTING THE OPERATION PARAMETERS
The operation parameters are set up with DIP-switches SW1. In the drive TR-3019-230E-ICU
SW1 is located on the unit board (Fig. 11). In the drive TR-3019-400E-ICU SW1 is located on
the optional module A1 of the unit (Fig. 12). Positions of the DIP-switches are described in table
4. The settings are described in table 5.
Y
ATTENTION! Operation parameters setup is performed when the drive is powered off (drive
mains switch is cut off the line)! The settings become activated when the power is restored.
DIP
DESCRIPTION
1
Operation mode
2
Safety edge type (SE input)
3
Activation of XP6 connector contacts
(operation of light signal device)
4
3 s delay of movement
5
Automatic verification of safety devices
connected to the input PH
6
Pause time before automatic closing
7
8
Automatic closing 5 s after PH input
activation
9
Failure of input SE to operate near the floor
10 Failure of input PH to operate at a distance
from the floor
DIP
SETTING
1
Operation mode
When the drive is delivered, all DIP-switches are in OFF position (factory settings).
*
In case of a failure or malfunctioning of safety devices when closing (inputs SE, PH).
**
38
38
Manual (without latching)
Resistive (8.2 kOhm)
Activation when the door
moves (signal lamp)
DESCRIPTION
In the manual operation mode press and hold the control button
to move the door to the correspondent end position (Fig. 13). If the button is
released, door leaf movement stops. To stop the movement or block the start
/ input S (table 2). Inputs SBS, PH and SE in the manual
of movement, press
operation mode are disabled.
In the pulse mode press the required control button
will move automatically to the corresponding end position end position. To stop
the movement, press
. Inputs SBS, PH and SE in the pulse operation mode
are enabled
SWITCH POSITION
OFF
*
Pulse (with latching) /
Manual mode in the closing
Optoelectronic (OSE)
Activation when the door is
fully opened (traffic light)
Disabled
Disabled
DIP № 6
DIP № 7
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Disabled
Off
Off
TR-3019-230E-ICU / TR-3019-400E-ICU
Table 4
ON
direction
**
Enabled
Enabled
Disabled
10 s
20 s
30 s
Enabled
On
On
Table 5
or
or
and the door