OPERATING INSTRUCTIONS – AS 210
ENGLISH
The control AS 210 is conceived to operate doors.
In the basic model, it is made for the dead man operation.
By means of plug-in modules, it can be extended individually.
SAFETY NOTICES
Please note valid directions and regulations of start-up of power operated doors in your
country.
Installation and maintenance works at control AS 210 should only be done by skilled
Electricians.
Note protecting prescriptions!
The installation has to be switched on free of tension during electrical works
Dead-man operation is only allowed if the installation can be seen from the control
devices.
If you do not respect the safety notices, you are responsible of resulting
personal and material damages.
CURRENT SUPPLY
In case of fixed connection, an all-polo main switch has to be foreseen.
In case of rotary current, only use triple block safety cut-out (10 A).
Please note that supply voltage corresponds with the data on type plate.
P
lease note that a clockwise rotatory field should be at the power outlet
Command and control should only be assembled inside buildings.
TECHNICAL DATA
Model
Tension
Frequency
Type of
protection
A max.
Operating temperature
17
AS 210
230V o
r 400V
50 Hz
IP 54
10 A
-10°C to +55°C
Revision_11_2007