Installation
Final Installation Considerations
Engine Oil
Any attempt to crank or start the
engine before it has been correctly filled with the
recommended oil will result in equipment failure and
service codes.
• Refer to Maintenance in the Operation section for oil fill
information.
• Damage to equipment resulting from failure to obey this
instruction will void the engine and generator warranty.
This engine ships from the factory pre-run and filled with
full synthetic oil (API SJ/CF 5W-30). This step allows for
system operation in a wide range of temperature and
climate conditions. Before starting the engine, check the
oil level as described in the Maintenance section.
Using full synthetic oil does not alter the required oil
change intervals as described in the Operation section.
Battery
WARNING
explosive hydrogen gas during recharging. The
slightest spark could ignite hydrogen and cause an
explosion, resulting in death or serious injury.
• DO NOT dispose of the battery in a fire. Recycle the
battery.
• DO NOT allow any open flame, spark, heat, or
lit cigarette in the area of the battery during the
battery-charging process and for several minutes
after charging.
WARNING
cause electrical shock or burns, resulting in death or
serious injury.
• A licensed professional must perform the
installation.
• Disconnect all sources of electricity before
installing or servicing equipment.
• Ground the system before applying power.
Part No. 80106286
Revision C
Storage batteries give off
Generator voltage could
WARNING
fluid contains acid and is extremely caustic. Contact
with battery contents could cause severe chemical
burns.
• DO NOT open or mutilate the battery.
• Wear protective goggles, a rubber apron, rubber
boots, and rubber gloves.
• Immediately wash electrolyte from skin with water.
• If electrolyte contacts the eyes, immediately flush
them with water and seek medical attention.
• Wash down spilled electrolyte with an acid-
neutralizing agent.
The installer must supply and install a rechargeable 12V
starting battery. The starting battery MUST conform to
the specifications shown in the following chart.
BATTERY SPECIFICATIONS
Specifications
Volts
Amps (Minimum) 540 CCA (Cold
Construction
Terminal Type
Dimensions
(Maximum)
WARNING
the generator may crank and start without warning,
resulting in death or serious injury.
• Do not connect the negative (-) cable at the battery
until the installation is complete.
Install the battery as described in Servicing the Battery in
the Maintenance section of this manual. Always connect
the negative cable last and secure the red positive
terminal insulator.
Use the supplied tie-down strap to secure the battery to
the unit. Attach each end of the strap to the existing tabs
in the base of the unit.
27
Final Installation Considerations
Battery electrolyte
Standard
Cold Start (Less
than 30° F / -1° C)
12VDC
12VDC
800 CCA (Cold
Cranking Amps)
Cranking Amps)
Wet Lead Acid
Wet Lead Acid
Top Post Type
Top Post Type
Battery
Battery
BCI Size 26 or
BCI Size 24
BCI Size 51
With the battery connected,