Fuel Consumption
The following chart shows estimated fuel supply
requirements at half and full load for natural gas and
liquefied petroleum vapor fuels.
NG Fuel
BTU/hr
1/2 Load
ft3/hr
BTU/hr
Full Load
ft3/hr
LP Fuel
BTU/hr
1/2 Load
ft3/hr
gal/hr
BTU/hr
ft3/hr
Full Load
gal/hr
Physical Properties
Normal Atmospheric State
Boiling Point (°F)
Heating Value:
BTU per gallon (Net LHV*)
BTU per gallon (gross**)
BTU per cubic feet (gas)
Density***
Weight
*
LHV (Low Heat Value) is the more realistic rating.
** Gross heat value does not consider heat lost in the
form of water during combustion.
*** Density is given in "Cubic Feet of Gas per Gallon of
Liquid. "
Weight is given in "Pounds per Gallon of Liquid. "
Part No. 80106286
Revision C
17 kW
20 kW
26 kW
170,000
187,000
206,000
170
187
206
248,000
260,000
323,000
248
260
323
17 kW
20 kW
26 kW
185,000
208,000
235,000
74
83
94
2.10
2.30
2.60
295,000
338,000
427,000
118
135
171
3.30
3.70
4.70
Natural
LP Vapor
Gas
Gas
Gas
-44
-259
83,340
63,310
91,547
2,500
1,000
36.39
57.75
4.24
2.65
Fuel Type
Consider the type of fuel that your generator uses, as it
affects the entire installation process. The system was
factory tested and adjusted using natural gas, but it
can be converted to use liquefied petroleum vapor. For
correct engine function, consider factors that affect each
of these fuels, such as the location and the duration of
possible utility interruptions. Follow these guidelines
when choosing fuel type:
• Use clean, dry fuel that is free of moisture or
any particulate material. Using fuels outside the
recommended values can cause performance
problems.
• In engines set up to run on propane (liquefied
petroleum), only use commercial-grade HD-5 propane.
Natural gas or LP engines are certified to operate on
natural or liquid propane gas. The emissions control
system for this engine is EM (Engine Modifications).
Fuel Pressure
Both LP vapor and natural gas fuel supply pressure at the
generator's fuel inlet port must be a minimum value at full
load with all gas appliances turned on and in operation.
Natural Gas must be 3.5-7 inches Water Column (WC).
Liquefied Petroleum must be 11-14 inches WC.
Ensure that all gas line shut-off valves are OPEN and that
adequate fuel pressure is available whenever automatic
operation is needed.