Briggs & Stratton 17 kW Manuel D'installation Et D'utilisation page 26

Groupe électrogène autonome monophasé refroidi à l'air
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Electrical Field Connections
Generator AC System Connection
The generator uses a single-phase, three-wire AC
connection system. The stator assembly consists of a
pair of stationary windings with two leads appearing
from each winding. The junction of leads 22 and 33 forms
the neutral lead, as shown schematically and as a wiring
diagram.
Neutral is not bonded to the ground at
the generator.
Only use the generator with a listed
transfer switch that is compatible with the generator.
22
Neutral
Circuit
Breaker
11
44
To Alternator
22
44
N
L2
To Transfer Switch
Figure 15
120V
120V
240V
To Chassis
Ground
11
0
Circuit
Breaker
L1
Grounding the Generator
Unless mandated by local code, additional chassis
grounding to earth at the generator is not required. Any
grounding at the generator must use metal piercing lock
washers (or their equivalent). Also, any listed terminals
must be installed per the terminal supplier's instructions.
All grounding and terminal installations must comply with
national electrical codes and local requirements.
Power Connections from the Generator to
the Transfer Switch
WARNING
generator from the utility power could result in death
or serious injury to electric utility workers due to the
backfeed of electrical energy.
• Use a listed transfer switch to connect to a
building's electrical system.
Utility Circuit Connection
Route all 240V utility leads in conduit. The 240V utility
leads deliver power to the generator's circuit board, and
optional battery, oil sump, and fuel regulator warmers.
This power also charges the battery. The generator starts
when power on these leads is lost. Using the installer-
supplied minimum 300V #14 AWG (2.50 mm2) wire,
connect each control circuit terminal in the generator
(25 and 26) to the fuse block in the automatic transfer
switch.
Generator Power Connection
Using the installer-supplied minimum 300V wires and the
table located in the Electrical Field Connections section,
connect the generator power output L1, L2, neutral (N),
and ground to the corresponding L1, L2, neutral (N), and
ground in the transfer switch.
Refer to the National Electric Code
(NEC) for correct electrical field connections and wire size
calculations.
26
Installation
Failure to isolate the
Part No. 80106286
Revision C

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

20 kw26 kw

Table des Matières