8. Control functions
8.1 Quick overview of control modes
AUTO
ADAPT
•
We recommend this control mode for most heating systems.
•
During operation, the pump automatically makes the necessary
adjustment to the actual system characteristic.
FLOW
ADAPT
The FLOW
control mode combines a control mode and a
ADAPT
function:
•
The pump is running in AUTO
•
The delivered flow from the pump will never exceed a selected
FLOW
.
LIMIT
Proportional pressure
•
This control mode is used in systems with relatively large pressure
losses in the distribution pipes.
•
The head of the pump will increase proportionally to the flow in the
system to compensate for the large pressure losses in the
distribution pipes.
Constant pressure
•
We recommend this control mode in systems with relatively small
pressure losses.
•
The pump head is kept constant, independent of the flow in the
system.
Constant temperature
In heating systems with a fixed system characteristic, for example
domestic hot-water systems, the control of the pump according to a
constant return-pipe temperature is relevant.
ADAPT
H
H
set1
A
1
H
auto_min
H
set2
A
A
3
2
H
25 %
Q
90 %
Q
max
max
H
fac
H
auto_min
Q
fac
H
H
set
H
set
2
H
H
For further
information, see
section
.
8.3.2 AUTO
ADAPT
Q
For further
information, see
section
.
8.3.3 FLOW
ADAPT
Q
For further
information, see
section
8.3.4 Proportional
pressure.
Q
For further
information, see
section
8.3.5 Constant
pressure.
Q
For further
information, see
section
8.3.6 Constant
temperature.
Q
21