CMFL
The power supply must meet the following requirements:
Connection
Fig. 10
Installing circuitry
Note
If used in safety-relevant applications, additional measures are necessary. In
Europe, for example, the standards in the EC machinery directive must be
observed.
Without additional measures in accordance with statutory minimum
requirements, the product is not suitable for use in safety-related sections of
control systems.
32
Voltage supply
Load voltage supply
(pin A1, A2)
– Nominal current
(max. permanent current)
– Peak current
Value
48 VDC ± 5 %
(optional: 24 VDC ± 5 %)
3 A
8 A
(at 48 VDC)
4.5 A
(at 24 VDC)
Festo – CMFL – 1304b English