65-410
The stairwell timer can be disabled via a lockable push button, which is placed in parallel with
the control.
Modifying the switch-off time (tp)
-> Press the push button 5 times in quick succession (intervals of max. 1s.).
-> The dimmer is in 'setting time' mode. This is indicated by the load continuously dimming up
and down.
-> In 'setting time' mode, you have 10s. to briefly press the push button 1 to 5 times in quick
succession.
Pressing the push button once corresponds to a switch-off time of 1min.
Pressing twice to 3min.
Pressing 3 times to 5min.
Pressing 4 times to 7min.
Pressing 5 times to 9min.
As a standard, the switch-off time is 3min.
-> After 10s., the 'setting time' mode will automatically be exited and changes are being saved.
Mode 2: 1-10V analogue control
Operation input 1 (terminals 3 - 4), adjusting the intensity:
When this mode is selected, the dimmer operates via a voltage control signal from 1 to 10V accord-
ing to the EN standard 60929. From 1 to 10V the light can be adjusted from 1% to maximum light
intensity. The intensity of the current of the control circuit determines the light level.
If the input voltage is less than the threshold voltage, the connected load will light at the set
minimum. If no control signal is connected, the connected load will light at the set maximum. If
the input voltage is 10V, the connected load will light at the set maximum. After a power cut, the
dimmer switches back to its previous value.
Operation input 2 (terminals 2 -3), switching the light on and off:
The connected load is switched on when the contact between input 2 and 'COM' is closed. If the
connection between input 2 and 'COM' is interrupted, the light will be switched off.
See connection diagram fig.6 with dim controller-receiver (05-350)