ε
65-410
R,L,C
If everything has been connected correctly and the power is switched on, all LEDs will light up
simultaneously for 1s.
A connected load can be operated manually by means of the select key. In 1-10V mode, the input
contact between terminals 2 and 3 must be closed. The select key functions as a single push
button control.
3. PROGRAMMING
As a standard, the dimmer is programmed as follows:
- automatic mode
- operation: 0-10V
- minimum is set to lowest possible intensity
- maximum is set to highest possible intensity
- single push button control set in memory mode
- light scene (single push button control) set to maximum value
These standard settings can be modified. To this end, the dimmer must first be put in programming
status. The programming status comprises the following 4 sections: mode (§A), input (§B), min (§C)
and max (§D). An associated LED indicates the section of the programming status that applies to
the dimmer. Putting the dimmer into programming status: Press the programming key for >2s. The
programming status always starts in section mode.
The dimmer is now in programming status and the load is switched on.
The order the different sections are passed through by repeatedly pressing the programming key
is as follows: mode, input, min, max.
Saving settings and exiting programming status: press the programming key for >2s.
If no action is performed in the programming status for 3min, the programming status will be
automatically exited without the modifications being saved.
EN
65