Télécharger Imprimer la page

Aprimatic CF10/2 Caractéristiques Techniques page 10

Publicité

Les langues disponibles
  • FR

Les langues disponibles

ENGLISH
3 Start-up
Caution:
Before starting, restore the connection between the membrane keypad on the cover of the
CF10/2 control unit and the control unit itself. Connect the membrane keypad earthing cable.
After making these connections, turn ON the mains supply and check that the system is operating
correctly.
3.1 Programming
Caution:
All the selections are enabled when you turn ON the device or when you press reset.
You can now program the control unit using DIP-SWITCH SW1, to select the push-button function, timing
of opening controlled by the thermostat, the type of functioning in the event of a power failure and whether
to have a buffer battery or not.
The tables below summarise the programming options.
SELECTION OF THE TYPE OF PUSH-
BUTTON FUNCTIONING
PUSH-BUTTON FUNCTION
DIP 1
ON
Maintained push-buttons
OFF
Spring-return push-buttons
SELECTION OF THE TYPE OF
FUNCTIONING IN EVENT OF POWER
FAILURE
DIP 4
LOGIC FUNCTION
(with buffer battery)
ON
Automatic opening and alarm signal
OFF
No function
SELECTION OF BUFFER BATTERY
PRESENCE/ABSENCE
BATTERY FUNCTION
DIP 6
ON
Battery not fitted
OFF
Battery fitted
The functions of DIP-Switches 4 and 5 are ONLY enabled if the buffer battery is installed. If the battery is
fitted, DIP-Switch 6 must be turned to OFF. If the battery is not fitted, DIP-Switch 6 must be turned to ON.
10
SELECTION OF THE THERMOSTAT OPENING
DIP 2
DIP 3
ON
ON
15 sec.
OFF
ON
30 sec.
ON
OFF
45 sec.
OFF
OFF
120 sec.
SELECTION OF THE TYPE OF
FUNCTIONING IN EVENT OF POWER
(SMOKE DETECTORS ENABLED)
DIP 5
ON
Automatic opening and alarm signal
OFF
No function
TIMING
Opening timing
FAILURE
LOGIC FUNCTION
(with buffer battery)

Publicité

loading