Commissioning the AC UPS

Supplement to the step-by-step instructions in section 4.4.7 of the operating instructions.
In order for DiagMonitor as of V4.5.1 or DiagBase as of V1.5.2 to report the status of the
UPS, the RUPS2000 software "Shutdown" setting must be set to "Use ACPI".
Remarque
The default action of Windows in response to a power failure of the UPS is: Hibernate.
See: ACPI -> Power Options -> Change plan settings -> Change advanced power settings ->
Battery
SIMATIC IPC847D
Instructions de service, 03/2018, A5E32997459-AC
IMPORTANT: Updated information for IPC847D
9.13 Commissioning the AC UPS
277