The monitor does not show
PROBLEM
the picture taken but shows an
image of the type:
Address : 1
Protocol
: MACRO
RS485-1:38400 N81 RX
RS485-2:38400 N81 REPEAT
232
: FW UPGRADE ONLY
FW: 0a (Jun 4 2009)
HW: 000-0001
DIP1.1: VIEW CONF. ON
Display Configuration dip-switch
CAUSE
rocker (DIP1, SW1).
SOLUTION
Switch off the pan & tilt, switch
down the dip-switch (DIP1, SW1).
Switch-on the unit again.
During start-up the pan & tilt is
PROBLEM
disabled and the following type
of message is shown:
Address : 1
DE-ICE PROCEDURE
IN PROGRESS...
REMAINING MINUTES:59
MNVCUCZ_1511_EN
The environment temperature is
CAUSE
too low.
SOLUTION
Wait until the end of the pre-heating
procedure. If the air temperature is
too low the unit will remain disabled
and the following message will be
shown:
Address : 1
DE-ICE PROCEDURE
------------------------
SYSTEM BLOCKED
TEMPERATURE TOO LOW
------------------------
Error E1-AUTOPAN WITHOUT
PROBLEM
LIMITS.
The two presets used as limits have
CAUSE
not been programmed.
SOLUTION
Program the two presets and then
update the Autopan configuration
menu (11.2 Saving a Preset, page 55
e 9.1.10.7 Autopan Menu, page 39).