USER INTERFACE BOARD

USER INTERFACE BOARD
Typical Motor Nameplate Showing Service Factor Amps (SF AMPS)
In this example, if controller is supplied with 208 V ,
use the 4.2 Amp Motor Overload Setting that is closest
to 4.2A without going over. For 230V input, use the setting
that is closest to 4.0A without going over.
6
Figure 3: UIB (User Interface Board)
Service Factor Amps (SF AMPS)
that are used to set the Motor
Overload Setting Dial.
Figure 4: Typical Motor Nameplate