Xylem CentriPro Aquavar ABII+ 3AB2 Manuel D'instruction page 5

Commande de pompe à vitesse variable
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Motor Wires – See Table 2
NOTE: SIZE WIRE AMPACITY FOR 75ºC COPPER
WIRE.
Refer to the Table 2 for wire sizing and maximum wire
lengths. Charts are designed to limit voltage drop to 5%.
Insure that the wire is rated for direct burial and/or
submergence.
Figure 2 shows the terminal block where the motor and
input wires connect. The circuit board near the terminal
block is labeled to show where to connect the motor wires.
For all motors, the green wire from the motor must be
attached to the terminal labeled GND.
For 2-wire, 1Ø motors with 2 black wires, connect one
black wire to each of the terminals labeled BLK and leave
the terminal labeled X empty. It doesn't matter which black
wire goes to which BLK terminal.
For 3Ø or 3-wire, 1Ø motors with red, black and yellow
wires, connect the red wire to RED, black wire to BLK and
yellow wire to YEL.
Input Power
SHOCK OR ELECTROCUTION
DANGER
HAZARD
Do not use this controller on a power supply
CAUTION
capable of delivering more than 5000 ARMS
symmetrical, 240V Maximum.
NOTE: SIZE WIRE AMPACITY FOR 75ºC COPPER
WIRE.
Connect a ground wire from the service panel to the
terminal marked GND. Controller has high leakage to
ground. Controller ground terminal must be connected to
the service entrance ground terminal. Failure to do so will
result in high voltage being present on the controller chassis.
Connect two "hot" wires from the 2 pole circuit breaker to
the terminals marked L1 and L2.
Table 2
Circuit
Model
Breaker
3AB2
30
5AB2
50
* Consult factory for selection of an output load filter (load reactor) for output wire lengths greater than 50 feet.
Circuit Breaker, Wire and Generator Sizing
1Ø Input Wiring
Size
Length (ft)
10 AWG
179
8 AWG
261
6 AWG
244
4 AWG
390
The input power system used must be a grounded power
system. The voltage measured from L1 to L2 must be in the
range of 196Vac to 265Vac. The voltage measured from
L1 to GND must be equal to the voltage measured from
L2 to GND. These voltages must be within the range of
120Vac +/- 10%. Reduced input voltage will reduce system
performance.
Do not use a Ground Fault Circuit Interrupter (GFCI) with
this product or nuisance tripping will result.
The use of Metal or Metallized Conduit with Metal
Conduit liquid tight connectors is recommended for all
electrical power connections.
Wire and Conduit
Factory installed input and output power leads may be
supplied with the controller. Size wire ampacity for 75º
C rated UL type copper wire. Use of Metal Conduit with
Metal Conduit liquid tight Connectors is recommended
for all electrical connections.
Input Power and Motor Lead Connections
L1
L2 GND
Incoming Power
Figure 2: Wiring Connections
3Ø Output Wiring*
Size
14 AWG
12 AWG
GND RED BLK YEL
Wires to Motor
Generator
Size
Length (ft)
(KW)
50
8100
50
13300
5

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Centripro aquavar abii+ 5ab2

Table des Matières