Offset Chimney Installation - Napoleon HIGH COUNTRY NZ6000-1 Instructions D'installation Et D'opération

Masquer les pouces Voir aussi pour HIGH COUNTRY NZ6000-1:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

18
4.4

OFFSET CHIMNEY INSTALLATION

EN
CHIMNEY SECTIONS INSTALLED BETWEEN AN OFFSET AND RETURN REQUIRE STRUCTURAL
SUPPORT TO REDUCE OFF-CENTER LOADING AND TO PREVENT CHIMNEY SECTIONS FROM
THE CHIMNEY SHOULD NOT BE BUILT WITH AN OFFSET ANGLE IN EXCESS OF 45° IN CANADA AND
30° IN USA. DO NOT COMBINE OFFSET CHIMNEY COMPONENTS TO EXCEED THESE ANGLES.
The first flue offset closest to the top of the unit must
be a minimum distance of 12" (304.8mm) from the top
of the appliance.
Attach an elbow to the chimney section, angled toward
the offset. Secure with 3 sheet metal screws.
To achieve the minimum offset, attach and secure a
second elbow. To achieve longer offsets, you may
install any available length of chimney pipe between
the elbows. Supports must be used on the first vertical
chimney section after a return elbow.
W415-1501 / 05.15.15
WARNING
!
SEPARATING AT THE CHIMNEY JOISTS.
Roof Joist
Storm Collar
Chimney Section
Elbow Support
Straps
Elbow
Firestop
63.6A
Rain Cap
Roof
Flashing
Attic Insulation
Shield
Elbow Support
Band
Elbow
Floor , Ceiling Joist
If the offset length is
more than 36"
(914.4mm), an
intermediate support
must be employed.
To achieve longer
offsets, you may
install any available
length of chimney
pipe between the
elbows.The
intermediate support
must be used in
conjunction with an
offset support.

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Nz6000-1

Table des Matières