SETTING THE TIME-OUT
Time-out is the amount of time that the motor remains enabled from when an
open or close command is issued. This time must always be longer than the
opening / closing time of the device. The time-out is reset only when the set time
elapses or after a stop.
Factory setting: 90 seconds
+
B
C
The time-out setting is retained even after the
memory is completely deleted.
TM2 R
A
28
A
90 s
B
45 s
C
180 s
2 sec.
A4516_6G66_Rev.A