Dismantling; Disposal - Maico ECA 100 ipro Instructions De Montage Et Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fault
Cause / Measure
Fan does not
No mains voltage.
switch on.
 Check whether the mains
fuse has failed. Switch on if
necessary.
Impeller blocked.
Fan does not
switch on.
 Should only be carried
out by a trained
electrician: Remove
cover [6]. Unlock internal
grille [5.1] or internal
shutter [5.2] using locking
hooks (see arrow) and
remove. Check impeller
and clean if necessary.
Fan does not
Overrun time
switch off.
(max. 25 minutes).
 Wait for the overrun time
and reduce if necessary,
see Chapter 8.5.
Motor's thermal
Motor too hot.
overload
protection
cooled. Cool-down time can
switches the
be up to 10 minutes. Unit
fan off.
switches back on automa-
tically after cooling.
Lamella do not
Lamella very dirty or
open or close
blocked.
for K units.
 Clean lamella.
 Check whether there
is anything between the
lamella. Remove if
necessary.
Wait until the motor has

12. Dismantling

Danger to life from electric
shock
 Dismantling may only be
DANGER
undertaken by an electrician.
 Switch off mains fuse before
removing.
Danger of burning due to
contact with bimetal (K units).
 Bimetal [5.3] is very hot after
CAUTION
fan is switched off. Do not
touch.
up to 10 minutes.
 Unlock covers (see arrow) and remove.
 Remove electronics cover [4] (3 latches).
 Remove power cable.
 Remove fan.

13. Disposal

Do not dispose of in domestic
i
waste.
The unit contains in part material that
can be recycled and in part
substances that should not end up as
domestic waste.
 Dispose of the unit once it has reached the
end of its working life according to the
regulations valid where you are.
GB