6.2. UNIT LOCATION

The unit base shall be arranged as indicated in the manual. There could be a risk of personal injury
or damage to property in the event of the unit being incorrectly supported.
1. The units are designed for installation above a suspended ceiling.
2. Install the unit in a location where the structure is capable of withstanding the weight of the unit.
3. Install the unit in a location which enable the unit's aeraulic inlet and outlet connections to be made.
4. Install the unit in a location providing for easy condensate evacuation.
5. Ensure that there is sufficient free space between the suspended ceiling and the solid ceiling for the
unit to be located.
6. Take care to leave adequate space around the unit for maintenance access (for minimum free space
on the service elevation for access to the filter and the fan motor assembly).
Do not install the unit in a machinery room or a kitchen where vapours or oil mist could
pass through the unit.
Do not install the unit in a laundry or in very damp areas (bathroom, sauna, etc.).

6.3. INSTALLATION INSTRUCTIONS

1. The unit is designed to be suspended on threaded rods or screw-spikes to be supplied by the installer.
The mounting lugs with slot type holes are fitted to the upper part of the unit.
2. Attach the 4 threaded rods or spike-screws to the solid ceiling in accordance with the diagram
opposite. Place 4 nuts and washers on each threaded rod.
3. Lift up the unit and slide the 4 threaded rods through the mounting lugs slots (the unit casing must
not touch the ceiling).
4. Attach the unit with 4 further firmly tightened washers, nuts and lock nuts. We recommend fitting
rubber blocks to prevent any risks of vibration be transmitted to the structure.
5. Lock the unit in its final location and level it off with a spirit level in order to guarantee correct
operation and condensate evacuation.
6. The unit must be installed so that the water drains towards the evacuation connection.
Mounting lugs
D
TOP VIEW
B
Unit size
1000
1500
2000
2500
4000
C
7
A
B
C
(mm)
(mm)
(mm)
580
37
27
680
37
27
780
37
27
880
37
27
1 180
37
27
D
(mm)
518
518
518
518
540