blueMatic EAV
NOTICE
•
Consider reserve cable (approx. 10 cm for all components)!
•
Correctly install the tappet contact with sash part and frame part regarding
polarity in DIN RS or LS door > opposite "+" or "-" (for DIN RS door "+" down,
for DIN LS door: "+" up).
Figure 3.3.1-2: Assignment of contacts, tappet contact
•
Correctly plug in each plug connector until they engage (secured to prevent
twisting).
•
Fasten on the profile for tappet contact and frame power supply with
screws, max. 4 x 20 mm (avoid damaging to the cable behind it).
•
Grease the sash part and frame part of the tappet contact prior to commissi-
oning and then on a regular base (see 4. Maintenance and care).
•
Test the function after installation of the tappet contact and frame power
supply.
CAUTION!
The cable for external signal on the frame power supply is live
(12 V DC); do not connect external voltage!
Insulated in condition as delivered; insulation is MANDATORY
when shortened (e.g. adaptation to the installation situation),
if not necessary.