blueMatic EAV
NOTICE
Consider reserve cable (approx. 10 cm for all components)!
Correctly install the tappet contact with sash part and frame part regarding
polarity in DIN RS or LS door > opposite "+" or "-" (for DIN RS door "+" down,
for DIN LS door: "+" up).
Figure 3.3.1-2: Assignment of contacts, tappet contact
Correctly plug in each plug connector until they engage (secured to prevent
twisting).
Fasten on the profile for tappet contact and frame power supply with
screws, max. 4 x 20 mm (avoid damaging to the cable behind it).
Grease the sash part and frame part of the tappet contact prior to commissi-
oning and then on a regular base (see 4. Maintenance and care).
Test the function after installation of the tappet contact and frame power
supply.
CAUTION!
The cable for external signal on the frame power supply is live
(12 V DC); do not connect external voltage!
Insulated in condition as delivered; insulation is MANDATORY
when shortened (e.g. adaptation to the installation situation),
if not necessary.
Aug. Winkhaus GmbH & Co. KG ∙ Berkeser Straße 6 ∙ 98617 Meiningen
T +49  369  3950 - 0 ∙ www.winkhaus.de ∙ Subject to technical changes
STK/RNT
Opening signal
(external)
-
0 V DC
+ 12 V DC
Fig.:
DIN right-hand, for installation
in DIN left-hand, rotate 180°
39
5051251
EN
3