Example of configuration
This example describes the principle of the procedure for integrating the device in the network
management tool RSNetWorx for DeviceNet (rev. 2.11.51.0) and the setting up of the process map of a
DeviceNet Master/Scanner.
Installation of the EDS file
Installation of the EDS file supplied on the diskette (bue8631.eds) is done with the aid of the tool EDS
Installation Wizard belonging to RSNetWorx. During the installation procedure, the icon also supplied on
the diskette can be allocated (if this is not done automatically).
Setting up the process map
Setting up the scanlist
First the Scanlist of the DeviceNet Master/Scanner is set up. For this purpose, the devices listed on the
left-hand part of the associated window are stored in the Scanlist on the right-hand side of the window.
Then for each device stored in the Scanlist, the desired I/O connection variant can be selected -
presetting is Polled.