Specifications
Power requirements 96D
Operating temperature range
Operating humidity range
Operating altitude
Network capacity
Communication
(length of lines)
User interface
Visual indicators
Outputs
Output rating
Audible alarm
Time delays
Battery
Enclosure
Dimensions (HxWxD)
Certifications
M-511401
8/10
17-27 Vac, 50/60 Hz, 8.64 VA
18-36 Vdc, 350mA @ 24 Vdc (8.4 VA)
-20°C to 50°C (-4°F to 122°F)
0 to 95% RH (non-condensing)
Up to 3000 m (9843 ft)
Up to 96 transmitters, 32 per channel
Channels 1, 2 = Modbus
Channel 3 = Modbus only
Up to 609m (2,000 ft) per channel
T-tap maximum = 20m (65 ft) per t-tap,
overall total of 40m (130 feet)
Graphic 122 x 32 dot matrix backlit display
User friendly keypad
Power
Green LED
Warn, Alarm, High Alarm Red LED
Fault
Tx
Rx
4 DPDT relays
5A, 30Vdc or 250 Vac (resistive load)
65dBA at 1 m (3 ft)
Programmable Before and After delays
3 volt lithium battery
Painted aluminum
9.5" x 14" x 3.5" (24.1 x 35.6 x 8.9 cm)
ANSI/UL 61010-1
CAN/CSA C22.2 No. 61010-1
ETL 116662