Supply voltage
Power consumption
Operating temperature
Operating humidity
Loop resistance
Output current
Detector
Alarm outputs:
Alarm setpoints
Maximum operating life
Shelf life
Detection range
Visual indicator
Sensor type
Detection technique
Cable
Pollution category
Installation category
Dimensions (DxWxH)
Weight
Certifications
511407
6/07
Specifications
10-28 Vdc (24 Vdc nominal)
50 mA minimum (with no alarm outputs)
24 mA @24 Vdc maximum
4 mA@24 Vdc nominal
0- 50 ºC (32-122 ºF)
15-90% RH (non-condensing)
650 Ohms maximum
Normal operation: 4-20 mA
Fault: 2 mA signal
Sensor expired: 2 mA signal
Over range: 24 mA signal (maximum)
4-20 mA transmitter c/w CO sensor
O/P1 (low alarm), O/P2 (high alarm)
0.25 A outputs activated by low and high gas
alarms and fault alarm
Each alarm not to exceed 250 mA @ 24Vdc
35 ppm and 200 ppm OSHA standard (special
setpoints available)
3 years
1 year
0-500 ppm
Red LED
Electrochemical cell
Instantaneous alarm
2-wire 18-24 AWG
2
I
3.5 x 4.5 x 6.5 cm (1.36" x 1.75" x 2.56")
38 g (1.34 oz.)
IEC No. 61010 (International Electrical Code)
ANSI/ISA S82.01
C22.2 No. 1010 (CS EC)
CSA File LR80259
ToxyPoint User Manual
Honeywell
Specifications