Electrical Installation - Burkert 8022 Guide De Démarrage Rapide

Transmetteur de débit / diviseur d'impulsions
Masquer les pouces Voir aussi pour 8022:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4-20 mA output
• Accuracy
• +/- 1,5% of the full scale
• Min. voltage drop at
• < 10 V at 20 mA
the device terminals
• max. 100 W at 12 VDC, max.
• Loop impedance
NPN/PNP output
open collector, 50 mA max.
current, 1-600 Hz frequency
Power consumption
< 200 mW
English
12
Fig. 1:
Installing Type 8022 on the sensor
English
14
700 W at 24 VDC, max.
1000 W at 30 VDC
7.
asseMBly, insTallaTion
7.1. assembly of Type 8022
note!
For the fault-free operation of the Type 8022 observe
the following during installation:
• When screwing to the sensor, ensure the seal is seated
correctly.
• Torque the screw to a value between 0.2 and 0.3 Nm,
in order not to damage the housing. With a damaged
housing, correct operation cannot be guaranteed.
Fig. 1: shows how Type 8022 is screwed to the sensor.

7.2. electrical installation

The electrical connection of the device is made on a terminal
strip via cable gland, or an M12 male fixed connector.
Terminal
assignment
1
NPN
2
PNP
3
12 - 30 V DC
4
GND
Fig. 2:
Terminal assignment, version with cable gland
Pin assignment
1
12 - 30 V DC
2
NPN
3
GND
4
PNP
Fig. 3:
Pin assignment, M12 male fixed connector
English
13
English
15